Select Page

Hazardous Location and Explosion Proof

7000 Series LED Super Explosion-Proof Signal Lights

Tomar Electronics introduces the Model 7000 family of LED super explosion-proof lights. These warning lights are UL listed for Class I, Division 1, Groups C & D; Class II, Division 1, Groups E, F & G; and Class III. They are available in five LED colors (Amber, Blue, Green, Red, and White).

Tomar’s super explosion-proof LED lights feature a unique thermal management system that utilizes internal cooling fins to draw heat away from the LED’s. This allows for longer lamp life and more consistent light output. All electronics and LED’s are guaranteed against manufacturing defects for a full 5 years.

An internal switch allows for easy selection among steady-burning, single or double flash mode. Each light will operate over a wide AC and DC input voltage range. The DC version is designed to operate from 10-36 VDC; the AC version from 85-265 VAC.

The full sized 7000 family series are constructed to NEMA 4X standards and are marine-rated for use in salt water environments. Design features include housing made of die cast high strength copper-free aluminum alloy with baked powder epoxy finish, stainless steel hardware, o-ring sealed prestressed glass dome with double pitch acme threads for smooth assembly and ease of maintenance.

Features
  • Super-Bright, high-power LED cluster for superior light output and greater lens fill
  • Unique Thermal Management System utilizes internal cooling fins to draw heat away from the LED’s. This allows for longer LED life and more consistent light output
  • DIP switch selectable single-flash, double-flash, or steady-burn mode
  • Order just the mounting style you need – Pendant, Flange (Ceiling), or Wall mount
LED Explosion Proof Models

Pendant Mount

Flange Mount

Wall Mount

Model Description Voltage
7024XLP pendant mount, 3/4” hubs 12-36 VDC
7124XLP pendant mount, 3/4” hubs 120-240 VAC
7024XLF flange mount, 3/4” hubs 12-36 VDC
7124XLF flange mount, 3/4” hubs 120-240 VAC
7024XLW wall mount, 3/4” hubs 12-36 VDC
7124XLW wall mount, 3/4” hubs 120-240 VAC
Specifications
Item Description
Lamp Type LED
Flash Rate 80 Single Flash per minute
40 Double Flash per minute
Voltage and Amperage 170 mA @ 24 VDC Flashing; 500 mA Steady-burn
035 mA @ 120 VAC Flashing; 100 mA Steady-burn
020 mA @ 240 VAC Flashing; 050 mA Steady-burn
In-rush Current 1.5 Amps @ 24 VDC Flashing and Steady-burn
065 mA @ 120 VAC
125 mA @ 240 VAC
Operating Temperature -40 C to 85 C
Temperature Code T6 – All voltage and temperature ranges
EPG Lens Guard
NFPA Definitions

Class I, Division 2.
A location (1) in which volatile flammable liquids or flammable gases are handled, processed or used, but in which the liquids, vapors or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems, or in case of abnormal operation of equipment; or (2) in which ignitable concentrations of gases or vapors are normally prevented by positive mechanical ventilation, and which might become hazardous through failure or abnormal operation of the ventilating equipment; or (3) that is adjacent to a Class I Division 1 location, and to which ignitable concentrations of gases or vapors might occasionally be communicated unless such communication is prevented by adequate positive–pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided. [See Section 500–4(b) of NFPA 70, National Electrical Code.]Class II, Division 2.
A location in which (1) combustible dust will not normally be in suspension in the air in quantities sufficient to produce explosive or ignitable mixtures and dust accumulations are normally insufficient to interfere with the normal operation of electrical equipment or other apparatus; or (2) dust may be in suspension in the air as a result of infrequent malfunctioning of handling or processing equipment and dust accumulations resulting therefrom may be ignitable by abnormal operation or failure of electrical equipment or other apparatus. [See Section 500–5 (b) of NFPA 70, National Electrical Code.]

Architect and Engineer Specifications

LED visual signaling beacon shall be Tomar model number series 7024 or 7124 or approved equal. The beacon shall be UL Listed Class I, Division 1, Groups C and D; Class II, Division 1, Groups E, F and G; and Class III for use in specified hazardous locations and /or combustible atmospheres as classified by the National Electric Code.
Operating voltage ranges shall be 10-36 VDC or 85-265 VAC. Operating temperature range shall be from -40 C to 85 C. Beacon shall have built-in selector switch to allow operation in Steady On, Single Flash, or Double Flash modes. Beacon must be rated NEMA 4X, with housing made of die cast high-strength copper-free aluminum alloy with baked powder epoxy finish, stainless steel hardware, O-ring sealed pre-stressed globe with double pitch acme threads for smooth assembly and ease of maintenance. The housing must be designed to accommodate a dome guard.